Standard Wiring Cables
Low Voltage (300/500 V)
PVC Insulated Sheathed Single Core
![]() | ![]() | ![]() |
Cable Approvals:
Cable approved to BS6004
Key Applications:
Fixed installation in dry or damp premises on walls, boards or trays, in channels or embedded in plaster.
Conductor:
Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 35.0mm²)
circular conductor complying with BS EN 60228 Class 1 or Class 2
Insulation:
PVC Insulation complying with BS EN 50363-3 Type Tl1
Core Identification:
red,black,blue,brown
Sheath:
PVC Sheath complying with BS7655 Type 6
Normally grey but others available on request
Voltage Rating: 300/500 volts, 120mm rated at 600/1000 volts
Temperature Rating: -15°C to +70°C
Minimum Bending Radius:
Up to 10mm2 - 3 x overall diameter
Above 10mm2 - 4 x overall diameter
Should not be installed at temperatures below 0°C or above +60°C.
Nominal cross Sectional area mm² | Stranding (mm) | No. Of Cores | Weight (Kg/Km) | Overall Diameter (mm) |
1 | 1/1.13 | 1 | 28 | 4.5 |
1.5 | 1/1.38 | 1 | 36 | 5.1 |
2.5 | 1/1.78 | 1 | 51 | 6 |
4 | 7/0.85 | 1 | 75 | 6.8 |
6 | 7/1.04 | 1 | 98 | 7.4 |
10 | 7/1.35 | 1 | 150 | 8.8 |
16 | 7/1.70 | 1 | 220 | 10.5 |
25 | 7/2.14 | 1 | 340 | 12.5 |
35 | 7/2.52 | 1 | 440 | 13.5 |
50 | 19/1.78 | 1 | 540 | 14.38 |
70 | 19/2.14 | 1 | 750 | 15.3 |
95 | 19/2.52 | 1 | 1010 | 17.7 |
120 | 37/2.03 | 1 | 1250 | 19.3 |